+ GENERATORS

1600REOZMD, 60 Hz

Fuel Type Diesel
Certification US EPA (Certified) Stationary Emergency
Standby Range (kW/kVA) 1160-1600/1050-1450
Prime Range (kW/kVA) 1450-2000/1313-1813
Frequency 60 Hz
Speed 1800 RPM
Alternator Type Brushless, Permanent-Magnet Pilot Exciter
Engine Manufacturer Mitsubishi

STANDARD FEATURES

  • KOHLER Co. provides one-source responsibility for the generating systems and accessories
  • The generator set and its components are prototype-tested, factory-built, and production-tested
  • A standard one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.

OTHER FEATURES

  • Kohler designed controllers for guaranteed system integration and remote communication
  • The low coolant level shutdown prevents overheating (standard on radiator models only)
  • An electronic, isochronous governor delivers precise frequency regulation
  • Multiple circuit breaker configurations

ALTERNATOR FEATURES

  • The pilot-excited, permanent-magnet(PM) alternator provides superior short-circuit capability
  • NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting
  • Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds and enables down stream circuit breakers to trip without collapsing the alternator field
  • Self-ventilated and drip-proof construction
  • Superior voltage waveform from a two-thirds pitch stator and skewed rotor and digital solid-state, volts-per-hertz voltage regulator with ±0.25% no-load to full-load regulation
  • Brushless alternator with brushless pilot exciter for excellent load response